Mfg Part Number: TRP1120
NSN : 5925-00-975-0975
NIIN : 009750975
CAGE Code : 24446
Manufacturer: General Electric Company
Item Name : Circuit Breaker
If you’re in need of NSN parts, Purchasing Synergy is the ultimate source. As an ASAP Semiconductor company, we have access to a vast and diverse inventory of parts and components like TRP1120 for the aerospace, civil aviation, defense, electronics, and industrial markets. This includes parts such as Circuit Breaker from General Electric Company with Cage Code 24446 as well as part numbers like TRP1120 and FSC 5925 Circuit Breakers with009750975. Purchasing Synergy has more than two billion new and obsolete parts readily available with short lead times and competitive prices and, as we are an AS9120B, ISO 9001:2015, and FAA AC 00-56B accredited business, and the only independent distributor with a No China Sourcing Pledge, each part we sell is fully traceable or comes directly from the manufacturer.
Our website offers a range of parametric search capabilities which allow our customers to search for parts through a number like TRP1120 and filters, one of which is National Stock Number, or NSN. A National Stock Number is an identifier applied to any item of supply that is repeatedly procured, stocked, stored, issued, and used throughout the federal supply system. Purchasing Synergy has a broad selection of NSN parts such as 5925009750975 from manufacturers like General Electric Company. To begin the purchasing process immediately, submit an RFQ today.
MRC | Criteria | Characteristic |
---|---|---|
ABHP | OVERALL LENGTH | 2.843 INCHES NOMINAL |
ABKW | OVERALL HEIGHT | 2.921 INCHES NOMINAL |
ABMK | OVERALL WIDTH | 0.968 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AKPX | POLE QUANTITY | 1 |
APNQ | ARC QUENCHING METHOD | DEION |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC SINGLE LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC SINGLE LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC SINGLE LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
CQQC | TRIP RELEASE DUTY CYCLE | CONTINUOUS SINGLE LOCATION |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 90.000 MINIMUM AT 150 PCT SINGLE LOCATION AND 200.000 MAXIMUM AT 150 PCT SINGLE LOCATION AND 30.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 55.000 MAXIMUM AT 200 PCT SINGLE LOCATION AND 14.000 MINIMUM AT 300 PCT SINGLE LOCATION AND 26.000 MA |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 25.0 DEG CELSIUS NOMINAL SINGLE LOCATION |
FEAT | SPECIAL FEATURES | MOUNTING TYPE IS TERMINAL |
FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
TTQY | TERMINAL TYPE AND QUANTITY | 1 SCREW AND 1 QUICK DISCONNECT, MALE |