Mfg Part Number: ETM4039
NSN : 5925-00-783-6221
NIIN : 007836221
CAGE Code : 30086
Manufacturer: Spd Electrical Systems Inc
Item Name : Circuit Breaker
If you’re in need of NSN parts, Purchasing Synergy is the ultimate source. As an ASAP Semiconductor company, we have access to a vast and diverse inventory of parts and components like ETM4039 for the aerospace, civil aviation, defense, electronics, and industrial markets. This includes parts such as Circuit Breaker from Spd Electrical Systems Inc with Cage Code 30086 as well as part numbers like ETM4039 and FSC 5925 Circuit Breakers with007836221. Purchasing Synergy has more than two billion new and obsolete parts readily available with short lead times and competitive prices and, as we are an AS9120B, ISO 9001:2015, and FAA AC 00-56B accredited business, and the only independent distributor with a No China Sourcing Pledge, each part we sell is fully traceable or comes directly from the manufacturer.
Our website offers a range of parametric search capabilities which allow our customers to search for parts through a number like ETM4039 and filters, one of which is National Stock Number, or NSN. A National Stock Number is an identifier applied to any item of supply that is repeatedly procured, stocked, stored, issued, and used throughout the federal supply system. Purchasing Synergy has a broad selection of NSN parts such as 5925007836221 from manufacturers like Spd Electrical Systems Inc. To begin the purchasing process immediately, submit an RFQ today.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-783-6221 Item Description: Circuit Breaker | 5925 | 007836221 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | 0 | ||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Etm4039 | 2 | 2 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 90.0 AMPERES AC ALL LOCATIONS AND 90.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 47.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 110.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 14.000 MINIMUM AT 300 PCT ALL LOCATIONS AND 29.000 MAXIMUM AT 300 PCT ALL LOCATIONS |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 50.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 SCREW |
ADTV | CASE MATERIAL | PLASTIC |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |